How to Determine the Right Wire Conductor Size for THWN and THHN?

  • ehsanallamii
  • Apr 7
  • 2 min read

Updated: May 6

What Are THHN and THWN Wires?

  • THHN stands for Thermoplastic High Heat-Resistant Nylon-coated wire. It's typically used in dry locations.

  • THWN is similar, standing for Thermoplastic Heat and Water-Resistant Nylon-coated. It’s rated for both wet and dry locations.

Most modern wires are dual-rated as THHN/THWN-2, meaning they meet both standards and can be used in nearly any environment.

How to Choose the Right Conductor Size

The size of the conductor depends on several factors:

  • Amperage load

  • Length of run (voltage drop considerations)

  • Temperature rating

  • Installation environment (wet, dry, conduit, etc.)

Here’s a quick reference chart based on the NEC ampacity guidelines (90°C rating in conduit, THHN/THWN-2 copper conductors):


THHN / THWN-2 Copper Wire Size & Ampacity Table

Wire Size (AWG or kcmil)

Conductor Diameter (inches)

Ampacity (90°C / 194°F)

Typical Breaker Size

Common Use

14 AWG

0.0641

25 Amps

15 Amps

Lighting, receptacles (residential)

12 AWG

0.0808

30 Amps

20 Amps

General circuits

10 AWG

0.1019

40 Amps

30 Amps

Water heaters, AC units

8 AWG

0.1285

55 Amps

40-50 Amps

Ovens, small subpanels

6 AWG

0.1620

75 Amps

60 Amps

Subpanels, car chargers

4 AWG

0.2043

95 Amps

70-90 Amps

Subfeeds, large appliances

3 AWG

0.2294

115 Amps

100 Amps

Larger subpanels

2 AWG

0.2576

130 Amps

125 Amps

Main feeders, heavy loads

1 AWG

0.2893

150 Amps

150 Amps

Main panel feeds

1/0 AWG

0.3249

170 Amps

175 Amps

Residential 200A service

2/0 AWG

0.3648

195 Amps

200 Amps

200A service entrance

3/0 AWG

0.4096

225 Amps

225 Amps

Large residential/commercial feeds

4/0 AWG

0.4600

260 Amps

250-300 Amps

Commercial panel feeds

250 kcmil

0.5085

290 Amps

300 Amps

Large industrial loads

300 kcmil

0.5491

320 Amps

350 Amps

High current feeders

350 kcmil

0.5873

350 Amps

400 Amps

Big service entrances

400 kcmil

0.6241

380 Amps

400-450 Amps

Large industrial feeders

500 kcmil

0.6981

430 Amps

450-500 Amps

Long distance high loads

600 kcmil

0.7677

475 Amps

500-600 Amps

High-demand facilities

750 kcmil

0.8620

535 Amps

600 Amps

Large-scale industrial power


 
 
 