How to Determine the Right Wire Conductor Size for THWN and THHN?
- ehsanallamii
- Apr 7
- 2 min read
Updated: May 6
What Are THHN and THWN Wires?
THHN stands for Thermoplastic High Heat-Resistant Nylon-coated wire. It's typically used in dry locations.
THWN is similar, standing for Thermoplastic Heat and Water-Resistant Nylon-coated. It’s rated for both wet and dry locations.
Most modern wires are dual-rated as THHN/THWN-2, meaning they meet both standards and can be used in nearly any environment.
How to Choose the Right Conductor Size
The size of the conductor depends on several factors:
Amperage load
Length of run (voltage drop considerations)
Temperature rating
Installation environment (wet, dry, conduit, etc.)
Here’s a quick reference chart based on the NEC ampacity guidelines (90°C rating in conduit, THHN/THWN-2 copper conductors):
THHN / THWN-2 Copper Wire Size & Ampacity Table
Wire Size (AWG or kcmil) | Conductor Diameter (inches) | Ampacity (90°C / 194°F) | Typical Breaker Size | Common Use |
14 AWG | 0.0641 | 25 Amps | 15 Amps | Lighting, receptacles (residential) |
12 AWG | 0.0808 | 30 Amps | 20 Amps | General circuits |
10 AWG | 0.1019 | 40 Amps | 30 Amps | Water heaters, AC units |
8 AWG | 0.1285 | 55 Amps | 40-50 Amps | Ovens, small subpanels |
6 AWG | 0.1620 | 75 Amps | 60 Amps | Subpanels, car chargers |
4 AWG | 0.2043 | 95 Amps | 70-90 Amps | Subfeeds, large appliances |
3 AWG | 0.2294 | 115 Amps | 100 Amps | Larger subpanels |
2 AWG | 0.2576 | 130 Amps | 125 Amps | Main feeders, heavy loads |
1 AWG | 0.2893 | 150 Amps | 150 Amps | Main panel feeds |
1/0 AWG | 0.3249 | 170 Amps | 175 Amps | Residential 200A service |
2/0 AWG | 0.3648 | 195 Amps | 200 Amps | 200A service entrance |
3/0 AWG | 0.4096 | 225 Amps | 225 Amps | Large residential/commercial feeds |
4/0 AWG | 0.4600 | 260 Amps | 250-300 Amps | Commercial panel feeds |
250 kcmil | 0.5085 | 290 Amps | 300 Amps | Large industrial loads |
300 kcmil | 0.5491 | 320 Amps | 350 Amps | High current feeders |
350 kcmil | 0.5873 | 350 Amps | 400 Amps | Big service entrances |
400 kcmil | 0.6241 | 380 Amps | 400-450 Amps | Large industrial feeders |
500 kcmil | 0.6981 | 430 Amps | 450-500 Amps | Long distance high loads |
600 kcmil | 0.7677 | 475 Amps | 500-600 Amps | High-demand facilities |
750 kcmil | 0.8620 | 535 Amps | 600 Amps | Large-scale industrial power |